EasyManuals Logo

Dräger P3U User Manual

Dräger P3U
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
23
Electrical connections
Installing fieldbus communication on the transmitter
The PROFIBUS PA transmission technology for intrinsically safe applications is
MBP. MBP stands for:
– Manchester Coding (M)
– Bus Powered (BP)
5 transmitters can be connected to a segment with a typical segment current of
100 mA.
Install the 4-wire connection cable in the cable gland, cut it to length and strip off
the insulation (approx. 80 mm).
Shorten the shield (if installed) to prevent short-circuiting.
Connect cable:
1 4-pin terminal block for Dräger Polytron 7000, observing the polarity.
2 4-pin terminal block for Dräger Polytron 7000, observing the polarity.
Slide connecting terminal back into holder.
Secure cable in holder.
Fold up the installation notes and place them in the Dräger docking station
for future use during commissioning.
Refit raincover (protection against dust and splashing water).
Installing the transmitter in 4-wire connection:
Caution:
With 4-wire connection the transmitter has no Ex protection. Once the
transmitter has been used after installation in this manner, it may never be
installed in explosion-hazard areas. Explosion hazard!
01323758_4.eps
1
X7 X8
2
FB –
FB +
+24 V
0 V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dräger P3U and is the answer not in the manual?

Dräger P3U Specifications

General IconGeneral
BrandDräger
ModelP3U
CategoryTransmitter
LanguageEnglish

Related product manuals