35
MAIN BELL
OUTPUT
SYSTEM AREA
MAIN BELL OUTPUT
The bell output on the main control board can be programmed to activate for any one of the 35
PGM output options on any number of partitions. The BELL terminal is normally 13.8 V
DC and will
switch to ground potential when activated. The BELL terminal will be at ground potential and
switch to 13.8 V
DC if any “INV” option is selected. If the bell output is not being used, a 1000 ohm
resistor (brown, black, red, gold) must be connected across the terminals as the output is
supervised.
Note: Refer to the PGM Outputs List for the available options.
MAIN BELL OUTPUT
(06)