49
PARTITION AREA
ADD/EDIT PAR
ADD/EDIT
PARTITIONS
Add/Edit Partition. Default settings has only the first partition enabled. To enable more partitions,
select the Add/Edit partition section, then select the partition. The partition is now enabled.
The PC4010 can be divided into 4 partitions. This section selects which of the 4 partitions the
installer is programming.
Each partition has its own 4 digit customer account number that will be transmitted to the
monitoring station when a reporting code is sent. The monitoring station can then identify the
customer. Where a zero digit is required, use Hex A to transmit ten pulses. The receiver at the
monitoring station interprets ten pulses as a zero. If a three digit code is required, enter [0] as the
last digit. [0] represents a null digit, no pulses will be transmitted.
Partition Toggles
Enabling or disabling options for individual partitions.
[F] Key Enabled?
YES = The [F]ire key is enabled.
NO = The [F]ire key is disabled.
(See “KEYPAD TOG OPT”.)
[A] Key Enabled?
YES = The [A]uxiliary key is enabled.
NO = The [A]uxiliary key is disabled.
(See “KEYPAD TOG OPT”.)
[P] Key Enabled?
YES = The [P]anic key is enabled.
NO = The [P]anic key is disabled.
(See “KEYPAD TOG OPT”.)
Display Clock?
YES = The time and date will be displayed on every keypad of the partition instead of the
“ENTER CODE TO ARM SYSTEM” message after 10 seconds of no key presses.
NO = No clock display.
Display Delay Exit Time?
YES = The exit delay time remaining will be displayed in the lower corner on all keypads on the
partition during the exit delay.
NO = No exit time display.
Bypass require code?
YES = Bypassing zones requires a valid access code ([Q][1][code]), either a System Master
code or an access code assigned to that partition.
NO = No access code required to bypass zones ([Q][1]).
Auto Arming/Auto Disarming?
YES = Auto Arm control enabled.
NO = Auto Arm control disabled. If disabled, the user will not be able to enter the Auto Arm
control menu in the [Q][6] user functions.
Note: The panel will not auto arm or auto disarm, if there is a loss of time trouble present on
the system.
Auto Arm Abort requires Access Code?
YES = An access code must be entered during the autoarm prealert to abort the auto arm.
NO = Pressing any key during the prealert will abort the auto arm.
Note: If the Auto Arm Abort Code is programmed it will be sent for one of these conditions.
Auto Arm Abort requires access code must be enabled for CTT arming to function properly.
ADD/EDIT PAR
(0)
WHICH PARTITION
(1)
(4)
CUSTOMER ID CODE
(0)
PAR TOGGLES
(1)
[F] ENABLED
Y
[A] ENABLED
Y
[P] ENABLED
Y
DISPLAY CLOCK
Y
DISP EXIT TIME
Y
BYPAS REQ CODE
Y
AUTOARM/DIS
Y
ABORT REQ CODE
N