Description of Controls
Page 63 of 90 057-233 ISSUE: 1
Once the load has been transferred to S2, it is not automatically transferred back to the S1 supply. To
manually transfer the load back to the mains either:
Pressing the Close/Open S1 button
Pressing the Auto button to return to automatic mode.
Pressing the Start Inhibit button to return to start inhibit mode.
For further details of breaker control, see the section entitled “controls and indications” elsewhere in
this manual.
4.8.3 STOPPING SEQUENCE
In manual mode, S2 continues to run until either:
Pressing the Start Inhibit button to return to start inhibit mode.
Pressing the Auto button to return to automatic mode.