40117 ~
40126
Registers 40117 to 40126 not shown. They
contain Active DTC No. 2 to 6 and are in the
same format as above.
40180 Previous Active DTC
lamp status and
reserved lamp status
0~65536 R
Bit 8~7 malfunction indicate lamp status
Bit 6~5 red stop lamp status
Bit 4~3 amber warning lamp status
Bit 2~1 protect lamp status
Low byte reserved for lamp status
40181 0~65536 R
40182
Previous Active DTC
No. 1 (Same format as
Active DTC registers
above)
0~65536 R
40183 ~
40244
Registers 40183 to 40244 are not shown. They
contain Previously Active DTC No. 2 to 32 and
are in the same format as above.
Same format as Active DTC
registers above.