6.5.1.1 on page 63.
LOSS OF ECM COMM J1939 messages required by the GSC400 have not
been received. The generator has shut down. See
section 6.1 on page 51.
LOW AIR PRESSURE The low air pressure digital input is active. See Table
15 on page 67.
LOW BATTERY Low battery voltage failure. See section 6.2 on page
54.
LOW COOLANT [Level] Low coolant level failure. See Table 15 on page 67.
LOW FUEL LEVEL Failure due to low fuel. See section 6.2 on page 54.
LOW HYDRAULIC Low Hydraulic digital input was active. See Table 15
on page 67.
LOW OIL LEVEL See section 6.2 on page 54.
LOW OIL PRESSURE See section 6.2 on page 54.
MAINTENANCE
NEEDED*
The generator requires maintenance. See section 6.11
on page 71.
MAINTENANCE
PERFORMED*
Maintenance has been performed on the generator
(i.e. the maintenance timer has been reset). See
section 6.11 on page 71.
MANUAL START* Generator started manually from the front panel RUN
key.
MANUAL STOP* Generator stopped manual from the front panel OFF
key.
OFF ENABLE* Front panel OFF key pressed to disable automatic
starting.
OPEN ENG TEMP
OPEN ENGINE TEMP
OPEN FUEL BASIN
OPEN FUEL LEVEL
OPEN OIL LEVEL
OPEN OIL PRES
Analog sender always reads the maximum voltage.
Could indicate that the sender is not connected to the
analog input (i.e. broken wire). See
OVER CRANK The engine RPM was too high. See section 6.3 on
page 58.
OVER CURRENT Over current failure. See section 6.4.3 on page 61.
OVER FREQUENCY Generator Frequency over the failure threshold. See
section 6.4.1 on page 59.
OVER SPEED Generator RPM too high. See section 6.3 on page 58.
OVER VOLTAGE Generator voltage high. See section 6.4.2 on page 59.
POWER ON* GSC400 was powered up from unpowered state.
REMOTE START*
REMOTE STOP*
The GSC400 was started / stopped from the remote
start contacts. See section 5.2 on page 21.
RS232 FAILURE
RS485 FAILURE
These are internal GSC400 failures. Try power cycle
the GSC400. If the failure occurs repeatedly the unit
could be defected.
SHORT ENG TEMP Analog sender reads zero volts or close to zero. This