CRANKING
WARMUP
CRANK REST
COOLDOWN
IDLE COOL (COOLDOWN IN IDLE)
LOW BATTERY PRELARM
LOW DC BATTERY CHARGING
EXERCISER PREALARM
EXERCISER RUNNING
4. DIGITAL I/O AND ANALOG INPUTS
(Read Only) Allows the status of the digital inputs and outputs to be read.
Digital I/O and Analog Input will update every 1 second once.
40110 Digital Input
0 ~ 1023 R (Read
Only)
Status of controller digital inputs. OFF
means the input is not active or not
connected.
Bit0 = Input A (BAT) 0 = OFF, 1 =
ACTIVE
Bit1 = Input B (BAT) 0 = OFF, 1 =
ACTIVE
Bit2 = Input C (BAT) 0 = OFF, 1 =
ACTIVE
Bit3 = Input D (BAT) 0 = OFF, 1 =
ACTIVE
Bit4 = Input E (GND) 1 = OFF, 0 =
ACTIVE
Bit5 = Input F (GND) 1 = OFF, 0 =
ACTIVE
Bit6 = Input G (GND) 1 = OFF, 0 =
ACTIVE
Bit7 = Input H (GND) 1 = OFF, 0 =
ACTIVE
Bit8 = Start/Stop 1 = OFF, 0 =
ACTIVE
Bit9 =Emergency Stop 0 = OFF, 1 =
ACTIVE
Note: Do not read the start/stop digital
input (Bit 8) as a means to determine if