97 of 105
40150 Engine Speed 0 ~ 6553.0 R
1 bit equal 0.1 RPM
Reading 18000
corresponds to 1800RPM
RPM
40151 High Engine
Temperature
0 ~ 250.0 R
1 bit equal 0.1 unit
Reading 1000 corresponds
to 100.0C
C
40153 Low Engine
Temperature
0 ~ 250.0 R
1 bit equal 0.1 unit
Reading 1000 corresponds
to 100.0C
C
40154 Fuel Level 0.0 ~ 100.0 R
1 bit equal to 0.1%
Reading 1000 corresponds
to 100.0%
%
40155 Oil Pressure 0.0 ~ 1000.0 R
1 bit equal 0.1 unit
Reading 1000 corresponds
to 100.0KPa
KPa
40156 Oil Level 0.0 ~ 100.0 R
1 bit equal to 0.1%
Reading 1000 corresponds
to 100.0%
%
40157 Fuel In Basin 0 ~ 100.0 R
1 bit equal to 0.1%
Reading 1000 corresponds
to 100.0%
%
40160 Line Voltage A-B R V
40161 Line Voltage B-C R V
40162 Line Voltage C-A R V
40163 Phase Voltage A R V
40164 Phase Voltage B R V
40165 Phase Voltage C
0~999.9
R
1 bit 0.1V
Reading 9999 corresponds
to 999.9.V
V
40167 Phase A Current R A
40168 Phase B Current R A
40169 Phase C Current
0~999.9
R
1 bit equal to 0.1A
Reading 9999 corresponds
to 999.9A
A
40170 AC Frequency 0 ~ 100.0 R
AC frequency
Reading 600 corresponds
to 60.0Hz
Hz
40172 ~
40173
Engine Hours (new -
f/w versions 2.02 and
above)
0~255999.9 R
32bit word: register 172 is
low 16bits, 173 is high
16bits. 1bit = 0.1 Hours
Hours
40174 Battery Voltage 0 ~ 31.8 R
1 bit equal 0.1V
V