Eaton 9355 Parallel UPS (10/15 kVA) User's Guide 164201601—Rev E0 21
Figure 12. Version 1 Internal Cover
Internal
Cover
7. Punch holes for the conduit (AC input, UPS output, load connection, and maintenance bypass contact
wires) using a Greenlee
®
punch or similar device.
8. Verify that the parallel bypass breaker is in the OFF position (see Figure 13).
9. Mount the parallel tie cabinet to the wall and install the conduit.
Figure 13. Version 1 Parallel Bypass Breaker
10. Verify that each UPS battery circuit breaker is in the OFF position (see Figure 14).
11. From each UPS, remove the UPS wiring access cover and one of the conduit landing plates and retain.
UPS System Installation