Eaton 9355 Parallel UPS (10/15 kVA) User's Guide 164201601—Rev E0 51
Table 6. User Settings
Description
Available Settings Default Setting
Set Date and Time
Set Month
Date: mm/dd/yyyy
Time: 24:00
01/01/2003
00:00
Display Contrast Adjust contrast with up/down arrow buttons Moderate
Change Language
Select Language: <English>
Elegir idioma <Español>
English
Set Nominal Output Voltage
Output:
[120V/208V] [127V/220V]
120V/208V
Relay Config
Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/
2/3/4]
Setup: [Battery Low] [On Battery] [On Bypass] [UPS
ok] [custom] [empty]
Alarm 1: empty
X-Slots (1 or 2)
#1: UPS ok
#2: On Bypass
#3: Summary Alarm
#4: On Battery
Signal Inputs
[empty] [Logic]
Signal Input must be wired to the CAN Bridge
Card.
For more information, refer to “Programmable
Signal Inputs” in the Eaton 9355 UPS (10/15 kVA)
User's Guide.
<empty>
Serial Port Config
Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
19200
Modem Config Modem Installation <Not Installed>
Set Modem Call Events
Event #0
Call modem: no
Set Modem Init String ATZ0
Set Modem Call Command None
Set Modem Communication Password
None
Start Screen
Eaton logo
Mimic screen
Eaton logo
User Password
Enabled/Disabled
If Enabled is selected, the password is USER.
Disabled
Audible Alarms Normal Sound/Disabled Normal Sound
Battery Charging ABM cycling/constant ABM cycling
Automatic Battery Tests
Enabled/Disabled
Enabled automatically runs the battery test once a
month.
Enabled
Full Power Battery Test Enabled/Disabled Enabled
Number of Battery Strings
0 through 22 2 strings for UPS-32 models