Eaton 9355 Parallel UPS (10/15 kVA) User's Guide 164201601—Rev E0 23
Figure 15. UPS Terminal Block (3-High Shown)
Ground
Maintenance
Bypass
Contacts
TB2
14. Hardwire the output terminations from the UPS to the parallel tie cabinet (see Figure 16).
Figure 16. Version 1 UPS Output to Parallel Tie Cabinet Wiring
Neutral
Line 1
Line 2
Line 3
Ground
15. Hardwire the load to the parallel tie cabinet (see Figure 17).
16. Wire the maintenance bypass contacts and terminate to the maintenance bypass wires in the parallel tie
cabinet (see Figure 15).
Connect the black and the red wire to TB2 on the UPS. Cap the blue wire.
NOTE The maintenance bypass contacts are normally-open. To ensure proper bypass
operation, DO NOT use the blue wire (it is normally-closed).