42 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide 164201601—Rev E0
Figure 38. Typical EBM Installation (2-High Cabinets Shown)
UPS Battery Connector
Rear Ground Strap
EBM Battery
Circuit Breaker
EBM Battery Connector
EBM Cable
UPS Battery Circuit Breaker
8. Remove the top front covers of all cabinets.
Press and release the handle latch at the bottom of the cover and then lift the cover up and off the cabinet.
9. Install the remaining ground straps between each cabinet (see Figure 39).
10. Reinstall the top front covers removed in Step 8.
Hang the top edge of the cover on the cabinet first, then lower the bottom edge and snap into place.
11. Proceed to Chapter 6 Operation to start up the UPS.
NOTE After UPS startup, ensure maximum battery runtime by configuring the UPS for the
correct number of EBMs (see paragraph 6.3 Configuring the UPS for EBMs).
UPS System Installation