Eaton 9355 Parallel UPS (10/15 kVA) User's Guide 164201601—Rev E0 39
44..33..44 SSttaabbiilliizziinngg tthhee CCaabbiinneett
NOTE 1 For seismic installations, you MUST order and install an Eaton 9355 UPS seismic kit; do
not use the following instructions.
NOTE 2 For non-seismic installations, you MUST install the stabilizing bracket on all 3-high
cabinets. The stabilizing bracket is optional for 2-high cabinets.
To stabilize the cabinet(s):
1. Lower the leveling feet to prevent the cabinet from rolling.
Figure 34. Lowering the Leveling Feet
2. Attach the stabilizing bracket to the bottom of the cabinet rear panel using the retained hardware from the
shipping pallet according to the cabinet configuration:
For one cabinet, see Figure 35.
For two cabinets, see Figure 36.
For three cabinets, see Figure 37.
NOTE No more than three cabinets can be attached together. For four cabinets, use two of the
two-cabinet installations. For five cabinets, use one three-cabinet and one two-cabinet
installation.
3. Use the holes and slots in the bottom of the bracket to attach the cabinet to the flooring if desired.
4. Continue to one of the following sections:
See paragraph 4.4 Extended Battery Module Installation to install optional EBMs.
See Chapter 6 Operation to start up the UPS.
NOTE After UPS startup, ensure maximum battery runtime by configuring the UPS for the
correct number of EBMs (see paragraph6.3 Configuring the UPS for EBMs).