22 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide 164201601—Rev E0
12. Punch two holes in the conduit landing plate for the input and output conduit using a Greenlee punch or
similar device.
Figure 14. UPS Rear View (3-High Shown)
Battery Circuit Breaker
UPS Wiring
Access Cover
Conduit Landing Plates
13. Hardwire the UPS input terminations.
See Table 4 for specifications and Figure 15 for a detailed view of the UPS terminal block.
NOTE 1 Input neutral must be wired for proper operation. Failure to connect an input neutral will
void the warranty. If the optional input transformer is installed, an input neutral is not
required.
NOTE 2 The Eaton 9355 UPS is a single-feed UPS only.
UPS System Installation