109
Copyright © 2021 Eaton Corporation plc. All rights reserved.
3. Unfasten the front door latch and swing the door open.
4. (If the UPS contains) Close the UPS output switch, bypass switch, and close the front door.
5. Repeat steps 3-5 for all UPSs in the system.
6.3.8. De-energizing the Critical Load
A UPS system Load O is initiated by the Load O button from Controls > System Controls
screen. This button can be pressed to control the UPS output. The Load O button de-energizes
the critical load and
Powers down the UPS system.
The UPS system (including Bypass) remains o until restarted.
1. Press Load O.
The shut down screen appears, providing a choice to proceed or abort the shutdown.
NOTE
All power to the critical load is lost when Load O is selected in the following step. You
should use this feature only when you want to de-energize the critical load.
2. To shut down the UPS, press Load O. To abort the shutdown, press ABORT. When Load
O is selected, the input, output, and bypass backfeed contactors open, the battery breaker
or disconnect is tripped, and all the UPSs in the system are turned o.
DANGER
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is
opened.
3. To restart the UPS system, follow the procedure in Section
6.3.1 Starting the UPS System in
Double Conversion Mode
or Section
6.3.2 Starting the UPS System in Bypass Mode
.