2.7. Basic System Congurations
UPS Power Rating
The power rating of a single UPS is determined by the number of UPM, but the maximum power could not
exceed the static bypass rating.
The UPS frames can be connected in parallel to create even larger systems. A maximum of four
300kW/600kW UPS frames can be connected in parallel and a maximum of two 1200kW UPS frame
can be connected in parallel. Above four UPS in parallel requirement can ask help from Eaton technical
solution team to customization design.
UPS Internal Options
The following table shows dierent standard and optional UPS options and the models where they apply.
Table 2-1: Standard and Optional UPS Options
300 kW 600 kW 1200 kW
Smart touch screen display for system
control and monitoring*
Standard Standard Standard
SNMP web interface (See
Section
5.1
) Option Option Option
Internal MBS* Standard (Internal) Standard (Internal) /
Rectier input switch*
Option Option
/
UPS output switch* /
Bypass switch* /
Integrated backfeed protection(K5)* Standard Standard Standard
Top Exhaust Accessory* Option Option Option
Single Input Option Option Option
Dual Input Standard Standard Standard
3-Wire/4-Wire* Option Option Option
Air lter Standard Standard Standard
*: Need to be assembled in the factory.
Additional options and accessories are also available. These include dierent software and connectivity
options and external switchgear and power distribution options.