Table 4-1: Signal Cables Connection Between the Primary Cabinet and the Secondary
Cabinet
Primary Abinet
Cable
Primary
Cabinet
Cable Mark
Secondary
Cabinet Cable
Mark
Secondary
Cabinet Cable
Position
IP CT Cable IP1 6PIN IP1 6PIN IP CT Cable Rear upper
OP CT Cable OP2 6PIN
OP2 6PIN OP CT Cable Rear
BYP Voltage
sampling cable
BYP1
BYP1
BYP Voltage
sampling cable
Rear
INPUT Voltage
sampling cable
INPUT1
INPUT1
INPUT Voltage
sampling cable
Rear
OUTPUT Voltage
sampling cable
OUTPUT2
OUTPUT2
OUTPUT Voltage
sampling cable
Rear
MC Signal cable MC1
MC1 MC Signal cable Rear
Parallel signal cable 8PIN
8PIN Parallel signal cable Rear
CUSTOMER CAN
Cable
CUSTOMER
CAN
CUSTOMER
CAN
CUSTOMER CAN
Cable
Lower front
4.2.1.2. Install Top Exhaust Accessory
1. Remove the rear upper covers of the cabinets;
See Figure 4-13
20
for the location of the
rear upper covers
2. Install the top exhaust accessories to the upper back of the cabinets, using M6*16 screws
(80pc), torque: 9Nm;
See Figure 4-13
6
for the location of the
top exhaust accessories
3. Connect the cables among the top exhaust accessories, the primary cabinet and the
secondary cabinet, detail please see
Table 4-2
;
4. Proceed to Section
4.2.1.3
.