EasyManua.ls Logo

Eaton 93PR - 6.4.3. Enabling and Disabling the Battery Charger; 6.5. UPM Control Instructions; 6.5.1. Adding;Reducing;Replacing Modules Online

Eaton 93PR
143 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
111
Copyright © 2021 Eaton Corporation plc. All rights reserved.
6.4.3. Enabling and Disabling the Battery Charger
To turn the battery charger on or o󰀨, perform the following procedure:
1. Press the Controls button in the main menu. The System controls screen appears.
2. On the System controls screen, press UPS controls.
3. Press the Start charger / Stop charger button.
6.5. UPM Control Instructions
6.5.1. Adding/Reducing/Replacing Modules Online
N+X is the most reliable power supply conguration at present. N represents the minimum
number of modules of the UPS that the total load needs; X represents the number of the
redundant modules of the UPS, i.e. the number of the fault modules that the system can handle
simultaneously. The bigger X is, the higher the system reliability is. The 93PR can be installed
up to twenty modules in its cabinet and the N+X parallel redundancy system can be congured
as 1+ 9 or 9 +1 etc multiple di󰀨erent modes. The UPM modules can be added, reduced and
changed online and the quantity of the N and X of the N+X parallel redundancy system can be
changed according to requirement at any time. When the modules fail, if only the quantity of the
fault modules is less than or equal to X, the fault UPM modules can be changed online without
a󰀨ecting the UPS running.
Options Supplied by the N+X Parallel Redundancy System
The 93PR can be installed from 1 up to 10 UPS modules in its cabinet and the user can choose
the N+X parallel redundancy solution easily. Suppose the load is 80kVA and the optional solution
is listed in the following table:
Installed
UPM
Permitted Maximum Power
Permitted Quantity of
the Fault UPS Modules
50kW Module 60kW Module
2 100kW 120kW 0
2+1 120(100)kW 120(100)kW 1
2+2 120(100)kW 120(100)kW 2
2+3 120(100)kW 120(100)kW 3
2+4 120(100)kW 120(100)kW 4
2+5 120(100)kW 120(100)kW 5
2+6 120(100)kW 120(100)kW 6
2+7 120(100)kW 120(100)kW 7
10 120(100)kW 120(100)kW 8
Note:
The “Permitted Maximum Power” does not mean that the UPS will be overloaded if this power value is exceeded.
For example, when selecting the 2+2 conguration, the rated UPS apparent power is 120(100)kVA and active

Table of Contents

Other manuals for Eaton 93PR

Related product manuals