Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
39
Copyright © 2021 Eaton Corporation plc. All rights reserved.
Table 3-7: Rated and Maximum Currents for Rated Power and Voltage (unit:A)
UPM QTY
Input Current Output current
Battery
(Rated)
Battery
(Max)
380 400 415 380 400 415
4*60kW 380 361 348 365 346 334 521
625
4*62.5kW
396 376 362 380 361 348 543 651
5*60kW 475 451 435 456 433 417 651
781
6*60kW 570 541 522 547 520 501 781
938
7*60kW 665 631 609 638 606 584 911
1094
8*60kW 760 722 696 729 693 668 1042
1250
8*62.5kW
791 752 725 760
722 696
1085 1302
9*60kW 855 812 783 820 779 751 1172
1406
10*60kW 950 905 870 915 870 835 1302
1563
11*60kW 1045 992 956 1003 953 918 1432
1719
12*60kW 1140 1083 1043 1094 1039 1002 1563
1875
13*60kW 1235 1173 1130 1185 1126 1085 1693
2031
14*60kW 1329 1263 1217 1276 1212 1169 1823
2188
15*60kW 1424 1353 1304 1367 1299 1252 1953
2344
16*60kW 1519 1443 1391 1459 1386 1336 2083
2500
17*60kW 1614 1534 1478 1550 1472 1419 2214
2656
18*60kW 1709 1624 1565 1641 1559 1503 2344
2813
19*60kW 1804 1714 1652 1732 1645 1586 2474
2969
20*60kW 1899 1804 1739 1823 1732 1669 2604
3125
NOTE
Bypass fuse type should be greater than 10 times rated I
2
t 20ms.