Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
125
Copyright © 2021 Eaton Corporation plc. All rights reserved.
8.5. UPS Environmental Specications
Table 8-5: UPS Environmental Specications
Ambient Service Temperature Range, (UPS) +0°C to +30°C*, No output power derating required.
Ambient UPS Storage Temperature Range From -25°C to +55°C in the protective package*
Maximum Service Altitude
Maximum 2000m (6600ft) with 1% derating per each
additional 100m.
Relative Humidity Range 5 to 95%, no condensation allowed
Acoustic Noise at 1 m
At 1m per ISO 7779 standard
300kW :
74.6dB
600kW :
78.8dB
1200kW :
81.8 dB
EMC IEC 62040-2 C3
*Maximum recommended operating and storage temperature with VRLA batteries is +25°C.
Storage condition for UPS and spare parts store one year (refer unit SN).
Place Indoor
Dusty Well
Storage Temperature <40°C
Storage Humidity < 70% RH
Other With original package
Please re –evaluate the storage time if can not meet above storage condition.