Eaton 93PR - Table 3-1: Dimensions and Weights

Eaton 93PR
143 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
Copyright © 2021 Eaton Corporation plc. All rights reserved.
The newer, more energy e󰀩cient data center cooling methods (such as air side economization)
can create much wider ranges of temperature and Relative Humidity (RH) in the UPS room and/
or data center.
There are two aspects of this increased operating environment that can, if ignored, create issues:
One is the creation of microclimates, which are persistent variations of temperature and/or
RH within a single room; for example one side of the room is always cooler than the other
side, no matter what the actual temperature is.
The other aspect is the rate of change of temperature and/or RH, which can occur during
transitions within the cooling system. Examples: changing the mixture ratio of inside versus
outside air, or external changes in the outside air when going from nighttime into day, and
back to night.
When ignored, either one of these aspects can create an undesirable microclimate at the UPS
location. If the environment created by this microclimate exceeds the Eaton UPS operating
specication, the UPS reliability, over time, will be reduced. These same environmental extremes
will also create reliability concerns for any servers that are exposed to them.
The UPS system installation must meet the following guidelines:
The system must be installed on a level oor suitable for computer or electronic equipment.
The oor must be suitable for heavy weight and wheeling.
The system must be installed in a temperature and humidity controlled indoor area free of
conductive contaminants.
The cabinet can be installed in line-up-and-match or standalone congurations.
The UPS equipment operating environment must meet the weight requirements shown in
Table 3-1
.
Table 3-1: Dimensions and Weights
Shipping dimensions
(WxDxH)
Cabinet dimensions
(WxDxH)WxDxH)
Shipping
weight
Installed
weight
300 kW
Rear Exhaust
Cabinet
900 x 1300 x 2200 mm 600 x 1100 x 2000 mm 465kg 375kg
Top Exhaust
Cabinet
1100 x 1300 x 2200 mm 798 x 1100 x 2000 mm 610kg 526kg
600 kW 1390 x 1220 x 2230 mm 1200 x 1100 x 2069 mm 907 kg 766 kg
1200 kW
Primary
Cabinet
1390 x 1220 x 2230 mm 1200 x 1100 x 2069 mm 900.5 kg 761.5 kg
Secondary
Cabinet
1390 x 1220 x 2230 mm 1200 x 1100 x 2069 mm 905.5 kg 766.5 kg
Accessory
Pack
1469 x 250 x 76 mm / 57 kg /
UPM 980 x 590 x 325 mm 439 x 700 x 174.2 mm 44 kg 39 kg
Top Exhaust Accessory
(a pair )
990 x 590 x 395 mm 443 x 432 x 275mm* 38.5 kg 13.6 Kg*
*:The dimension and weight of a single top exhaust accessory.