EasyManua.ls Logo

Eaton 93PR - 3.3.1. UPS System Power Wiring Preparation

Eaton 93PR
143 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
Copyright © 2021 Eaton Corporation plc. All rights reserved.
3.3.1. UPS System Power Wiring Preparation
NOTE
If installing a maintenance bypass, a minimum of two separate feeds with upstream
feeder breakers, or a single feed with two upstream feeder breakers, must be provided:
one for the UPS or rectier input breaker (if installed) and one for the maintenance bypass
input. DO NOT use a single feed or a single feeder breaker to supply both the UPS or
rectier input breaker and the maintenance bypass. If a bypass input breaker is installed
in the maintenance bypass and a single-feed UPS is being installed, a single feed to the
maintenance bypass is acceptable for supplying both the UPS and the bypass.
Read and understand the following notes while planning and performing the installation:
Refer to national and local electrical codes for acceptable external wiring practices.
To allow for future kVA upgrades (software and/or hardware), consider using conductors
sized for full bypass rating of the UPS.
Material and labor for external wiring requirements are to be provided by designated
personnel.
For external wiring, use 90°C copper wire. See the appropriate information in
Table 3-4
. Wire
sizes are based on using the specied breakers.
If wire is run in an ambient temperature greater than 30°C, higher temperature wire and/or
larger size wire may be necessary.
Specication is for copper wire with a 90°C rating.
4-wire system:
The input uses three live wires and N wires, plus a grounding wire (protective grounding
conductor).the phases must be symmetrical about ground (from Y-type/Wye source) for
proper equipment operation.
Support the load that needs to take N wire.
If the neutral wire is disconnected, all phase wires should be disconnected at the same time.
3-wire system:
The input uses three live wires and grounding wires (protective grounding conductors).
Without the N-line, it does not support the load that requires the N-line.

Table of Contents

Other manuals for Eaton 93PR

Related product manuals