8.3. UPS System Output
Table 8-3: UPS System Output
Number of Output Phases 3 phases + N (Optional)
Rated Output Voltage 220/380 V; 230/400 V; 240/415 V, congurable
Total Voltage Harmonic Distortion
100% Linear Load < 1%
100% Non-Linear Load < 5%
Rated Output Frequency
Output Frequency Variation
Slew Rate
50 or 60 Hz, congurable
± 0,1 Hz
1 Hz/s
Overload Capability at Ambien 30°C
(Ambient Temperature)
10 min 125% load
Overload Capability at Ambient 30°C
(Double Conversion Mode)
60 min 102-110 % load
10 min 111-125 %
30 sec 126-150 % load
300 ms > 150 % load
Overload Capability at Ambient 30°C
(on Inverter, Stored Energy Mode)
1 min 102-110 % load
300 ms > 110 % load
Overload Capability at Ambient 30°C
(on Bypass)
Continuous < 115% load,
10 ms 1000% load
Note! Bypass fuses may limit the overload capability.
Output Current
See Table 3-6 Rated and Maximum Currents for Rated
Power and Voltage (unit:A)
Load Power Factor, (Rated) 1.0
Load Power Factor, (Permitted Range) From 0.8 lagging to 0.8 leading