Maintenance and Alarms
Eaton ePDU G3 Operation Manual P-164000277—Rev 5 132
2 215200 ePDU Input 2 Low Voltage Critical The specified section voltage reading is less than the
value configured as the low voltage critical threshold.
2 215300 ePDU Input 2 High Voltage Warning The specified section voltage reading is greater than
the value configured as the over voltage warning
threshold.
2 215400 ePDU Input 2 High Voltage Critical The specified section voltage reading is greater than
the value configured as the over voltage critical
threshold.
2 216000 ePDU Input 2 Frequency OK The frequency is not out of range.
2 216100 ePDU Input 2 Frequency out of +/- 3 Hz
tolerance
The frequency is out of range.
2 221000 ePDU Gang Phase Input Current No
Threshold
No section current threshold has been triggered.
2 221100 ePDU Gang Phase Low Current Warning The current amperage (A) reading for the specified
section is less than the value configured as the low
current warning alarm threshold.
2 221200 ePDU Gang Phase Low Current Critical The current amperage (A) reading for the specified
section is less than the value configured as the low
current critical alarm threshold.
2 221300 ePDU Gang Phase Over Current Warning The specified section current amperage (A) reading is
greater than the value configured as the over current
warning threshold.
2 221400 ePDU Gang Phase Over Current Critical The specified section input current amperage (A)
reading is greater than the value configured as the
over current critical alarm threshold.
2 222000 ePDU Gang Phase Voltage No Threshold No section voltage threshold has been triggered.
2 222100 ePDU Gang Phase Low Voltage Warning The specified section voltage reading is less than the
value configured as the low voltage warning
threshold.
2 222200 ePDU Gang Phase Low Voltage Critical The specified section voltage reading is less than the
value configured as the low voltage critical threshold.
2 222300 ePDU Gang Phase Over Voltage Warning The specified section voltage reading is less than the
value configured as the over voltage warning
threshold.
2 222400 ePDU Gang Phase Over Voltage Critical The specified section voltage reading is less than the
value configured as the over voltage critical
threshold.
2 223000 ePDU Gang Not Alarmed No alarm has been triggered.
2 223100 ePDU Gang Alarmed An alarm has been triggered.
2 241000 Communication OK No communication failure detected on Teridian
RS-485 bus
2 241100 Communication Lost Communication failure detected on Teridian RS-485
bus
2 251000 Daisy Chain Communication OK No communication failure detected on Daisy Chain
2 251100 Daisy Chain Communication Alarmed Communication failure detected on Daisy Chain
2 231000 ePDU Outlet Current No Threshold No outlet current threshold has been triggered.
Table 11. ePDU and User Alarms and Events (Continued)
Type Code
Identification and
Index Code Alarm or Event Description