Maintenance and Alarms
Eaton ePDU G3 Operation Manual P-164000277—Rev 5 131
2 207400 ePDU Temperature Critical High Threshold The temperature level reading is greater than the
value configured as the high temperature critical
threshold.
2 211000 ePDU Input 1 Current No Threshold No section current threshold has been triggered.
2 211100 ePDU Input 1 Low Current Warning The current amperage (A) reading for the specified
section is less than the value configured as the low
current warning alarm threshold.
2 211200 ePDU Input 1 Low Current Critical The current amperage (A) reading for the specified
section is less than the value configured as the low
current critical alarm threshold.
2 211300 ePDU Input 1 Over Current Warning The specified section current amperage (A) reading is
greater than the value configured as the over current
warning threshold.
2 211400 ePDU Input 1 Over Current Critical The specified section current amperage (A) reading is
greater than the value configured as the over current
critical alarm threshold.
2 212000 ePDU Input 1 Voltage No Threshold No section voltage threshold has been triggered.
2 212100 ePDU Input 1 Low Voltage Warning The specified section voltage reading is less than the
value configured as the low voltage warning
threshold.
2 212200 ePDU Input 1 Low Voltage Critical The specified section voltage reading is less than the
value configured as the low voltage critical threshold.
2 212300 ePDU Input 1 Over Voltage Warning The specified section voltage reading is greater than
the value configured as the over voltage warning
threshold.
2 212400 ePDU Input 1 Over Voltage Critical The specified section voltage reading is greater than
the value configured as the over voltage critical
threshold.
2 213000 ePDU Input 1 Frequency OK Utility frequency is within the +/- 3 Hz of Nominal
frequency.
2 213100 ePDU Input 1 Frequency Out of Range Utility frequency greater or less than +/- 3 Hz of
Nominal frequency.
2 214000 ePDU Input 2 Current No Threshold No section current threshold has been triggered.
2 214100 ePDU Input 2 Low Current Warning The current amperage (A) reading for the specified
section is less than the value configured as the low
current warning alarm threshold.
2 214200 ePDU Input 2 Low Current Critical The current amperage (A) reading for the specified
section is less than the value configured as the low
current critical alarm threshold.
2 214300 ePDU Input 2 High Current Warning The specified section current amperage (A) reading is
greater than the value configured as the over current
warning threshold.
2 214400 ePDU Input 2 High Current Critical The specified section current amperage (A) reading is
greater than the value configured as the over current
critical alarm threshold.
2 215000 ePDU Input 2 Voltage No Threshold No section voltage threshold has been triggered.
2 215100 ePDU Input 2 Low Voltage Warning The specified section voltage reading is less than the
value configured as the low voltage warning
threshold.
Table 11. ePDU and User Alarms and Events (Continued)
Type Code
Identification and
Index Code Alarm or Event Description