Maintenance and Alarms
Eaton ePDU G3 Operation Manual P-164000277—Rev 5 130
Figure 97 provides an example of a Type Code 2 ePDU alarm number code.
Figure 97. Example Type 2 Code
Table 11 lists ePDUand User alarms and events.
Table 11. ePDU and User Alarms and Events
Type Code
Identification and
Index Code Alarm or Event Description
2 201000 Dry Contact 1 Not Active The signal for Dry Contact 1 is active.
2 201100 Dry Contact 1 Active The signal for Dry Contact 1 is not active.
2 202000 Dry Contact 1 Open Dry Contact 1 is open.
2 202100 Dry Contact 1 Closed Dry Contact 1 is closed.
2 203000 Dry Contact 2 Not Active The signal for Dry Contact 2 is active.
2 203100 Dry Contact 2 Active The signal for Dry Contact 2 is not active.
2 204000 Dry Contact 2 Open Dry Contact 2 is open.
2 204100 Dry Contact 2 Closed Dry Contact 2 is closed.
2 205000 Sensor Probe Communication Failure Cleared Sensor Probe communication failure is cleared
2 205100 Sensor Probe Communication Failure Sensor probe communication failure detected
2 208000 Sensor Probe Not Connected Sensor probe not connected since firmware startup
2 208100 Sensor Probe Connected Sensor probe connected at least once since firmware
startup
2 206000 Humidity No Threshold No humidity threshold has been triggered.
2 206100 Humidity Warning Low Threshold The humidity level reading is less than the value
configured as the low humidity warning threshold.
2 206200 Humidity Critical Low Threshold The humidity level reading is less than the value
configured as the low humidity critical threshold.
2 206300 Humidity Warning High Threshold The humidity level reading is greater than the value
configured as the high humidity warning threshold.
2 206400 Humidity Critical High Threshold The humidity level reading is greater than the value
configured as the high humidity critical threshold.
2 207000 Temperature No Threshold No temperature threshold has been triggered.
2 207100 Temperature Warning Low Threshold The temperature level reading is less than the value
configured as the low temperature warning
threshold.
2 207200 Temperature Critical Low Threshold The temperature level reading is less than the value
configured as the low temperature critical threshold.
2 207300 Temperature Warning High Threshold The temperature level reading is greater than the
value configured as the high temperature warning
threshold.
2
1
14
02
Number code 211402: Eaton ePDU Critical Overcurrent L2 Phase
Identication code = 114
Index code = 02
Type code 2 = Eaton ePDU