Responding to System Events
12-5
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
NOTICES
Message
Horn Phone Relay Log*
Indication
Automatic Shutdown Pending 1 No No A Information Only
Automatic Shutdown Pending O K OFF No No A Condition Cleared
Automatic Startup Pending 1 No No A Information Only
Battery Current Limit 1 No No HA Information Only
Battery Current Limit OK Off No No HA Condition Cleared
Battery Voltage High 1 1 No HA Information Only
Battery Voltage High OK Off No No HA Condition Cleared
Battery Voltage Low 1 No No HA Information Only
Battery Voltage Low OK Off No No HA Condition Cleared
Bypass AC O ver Voltage 1 No No HA Information Only
Bypass AC O ver Voltage OK Off No No HA Condition Cleared
Bypass AC Under Voltage 1 No No HA Information Only
Bypass AC Under Voltage OK Off No No HA Condition Cleared
Bypass Phase Rotation 1 No No HA Information Only
Bypass Phase Rotation OK Off No No A Condition Cleared
Bypass Source Out of Tolerance 1 No No HA Investigate UPS
Bypass Source Out of Tolerance OK Off No No HA Condition Cleared
BypassUnderorOverFrequency 1 No No HA Information Only
BypassUnderorOverFrequencyOK Off No No HA Condition Cleared
Charger Off Command 1 No No HA Information Only
Charger On Command 1 No No HA Information Only
ChargerOverVoltageorCurrent 1 No No HA Information Only
Charger Tripped 1 No No HA Information Only
Charger Tripped OK Off No No HA Condition Cleared
Check Battery 1 No No HA Information Only
Check Battery OK Off No No HA C ondition Cleared
Check Modem 1 No No HA Information Only
Check Modem OK Off No No HA Condition Cleared
DC Link Over Voltage 1 1 No HA Information Only
DC Link Over Voltage OK Off No No A Condition Cleared
DC Link Under Voltage 1 No No HA Information Only
DC Link Under Voltage OK Off No No HA Condition Cleared
Emergency Transfer To Bypass 1 No No HA Information Only
Emergency Transfer To Bypass OK Off No No A Condition Cleared
*Log codes indicate where the UPS records the event: H = History log; HA = History and Active logs; and
A=Activelogonly.