Responding to System Events
12-6
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
NOTICES
Indication
Log*RelayPhoneHorn
Message
Input AC Over Voltage 1 No No HA Information Only
Input AC Over Voltage OK Off No No HA Condition Cleared
Input AC Under Voltage 1 No No HA Information Only
Input AC Under Voltage OK Off No No HA Condition Cleared
Input Phase Rotation 1 No No HA Information Only
Input Phase Rotation OK Off No No HA Condition Cleared
Input Under or Over Frequency 1 No No HA Information Only
Input Under or Over Frequency OK Off No No HA Condition Cleared
Inv Under or Over Frequency 1 No No HA Information Only
Inv Under or Over Frequency OK Off No No HA Condition Cleared
Inverter AC Over Voltage 1 No No HA Information Only
Inverter AC Over Voltage OK Off No No HA Condition Cleared
Inverter AC Under Voltage 1 No No HA Information Only
Inverter AC Under Voltage OK Off No No HA Condition Cleared
Inverter Off Command 1 No No A Information Only
Inverter On Command 1 No No HA Information Only
Inverter Output Overcurrent 1 No No HA Information Only
Inverter Phase Rotation 1 No No HA Information Only
Inverter Phase Rotation OK Off No No HA Condition Cleared
Load Dumped (Load Power Off) 1 1 No HA Investigate UPS
Load Dumped (Load Power Off) OK Off No No HA Condition Cleared
Load Off Command Executed 1 No No HA Information Only
Load Power On Command 1 No No HA Information Only
Load Power On Command Received 1 No No HA Information Only
Loss of Redundancy 1 No No HA Information Only
Loss of Redundancy OK Off No No HA Condition Cleared
Maintenance Bypass Mode 1 No No HA Information Only
Modem Call Completion Failed 1 No No HA Information Only
Neutral Current Limit 1 No No HA Information Only
Neutral Current Limit OK Off No No HA Condition Cleared
Non -Volatile Memory Failure 1 No No A Information Only
Non -Volatile Memory Failure OK Off No No A Condition Cleared
Output AC Over Voltage 1 No No HA Information Only
Output AC Over Voltage OK Off No No HA Condition Cleared
*Log codes indicate where the UPS records the event: H = History log; HA = History and Active logs; and
A=Activelogonly.