Responding to System Events
12-7
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
NOTICES
Indication
Log*RelayPhoneHorn
Message
Output AC Under Voltage 1 No No HA Information Only
Output AC Under Voltage OK Off No No HA Condition Cleared
OutputUnderorOverFrequency 1 No No HA Information Only
OutputUnderorOverFrequencyOK Off No No HA Condition Cleared
Rectifier Current Over 125% 1 No No A Information Only
Rectifier Input Over Current 1 No No A Information Only
UPS Module Off 1 No No A Information Only
UPS Module Off OK Off No No A Condition Cleared
UPS on Battery 1 No No A Investigate UPS
UPS on Battery OK Off No No A Condition Cleared
UPS on Bypass 1 No No A Investigate UPS
UPS on Bypass OK Off No No A Condition Cleared
UPS on Generator 1 No No A Information Only
UPS on Generator OK Off No No A Condition Cleared
*Log codes indicate where the UPS records the event: H = History log; HA = History and Active logs; and
A=Activelogonly.