3 Installation
3.6 Electrical Installation
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 99
3.6.1.6 Connecting the motor cable
The screened cables between the variable frequency drive and the motor
should be as short as possible.
Figure 65:Connection on motor side
Connect the screening, on both sides and across a large area
(360° overlap), to the protective earth (PE) . The power screening’s
protective earth (PES) connection should be in the immediate proximity
of the variable frequency drive.and directly on the motor terminal box.
Prevent the screen earth kit from becoming unbraided, i.e. by pushing
the separated plastic covering over the end of the shielding or with a
rubber grommet on the end of the shielding. Terminate the cable screen
across a large area at the end (PES).
Alternatively, you can twist the screen braid and connect it to the
protective earth with a cable lug. In order to prevent EMC interference,
this twisted screen connection should be as short as possible
(recommended value for the twisted cable screen: b 1/5 a).
Figure 66:Screened connection cable in motor circuit