6 Technical Data
6.5 Fuses
164 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
6.5 Fuses
The Eaton circuit-breakers and fuses listed below are examples and can be
used without additional measures. If you use other circuit-breakers and/or
fuses, make sure to take their protection characteristic and operational
voltage into account. When using other circuit-breakers, it may be necessary
to also use fuses depending on the circuit-breaker’s model, design, and
settings. There may also be limitations concerning the short-circuit capacity
and the supply network’s characteristic, and these must also be taken into
account when selecting circuit-breakers and/or fuses.
Table 30: Protective devices
Symbol
Description
Miniature circuit breakers
FAZ-B…/1N: 1 pole + N
FAZ-B…/2: 2 pole
FAZ-B…/3: 3 pole
Rated operating voltage: 230/400 V AC
Switching capacity: 15 kA
Motor-Protective Circuit-Breakers
PKM0…, PKZM4…: 3 pole
Rated operating voltage: 690V AC
Switching capacity:
PKM0: 150 kA to 12 A and 50 kA to 32 A
PKZM4: 50 kA
Circuit-breaker
NZMC…: 3 pole
Rated operating voltage: 690V AC
Switching capacity: 36 kA
Fuse
Rated operating voltage: 500V AC
Switching capacity: 50 kA
Size: DII, E27 / DIII, E33
Fuse base: S27… / S33…
Fuse Class J
Rated operating voltage: 600V AC
Switching capacity: 300 kA
Fuse bases:
up to 30 A: J60030…
35 - 60 A: J60060…
70 - 100 A: JM60100…
110 - 200 A: JM60200…
225 - 400 A: JM60400…
450 - 600 A: JM60600…
Fuse gG
Rated operating voltage:
400 V AC (NHG…B-400)
500 V AC (NHG…B)
660 V AC (NHG…B-660)
690 V AC (NHG…B-690)
Switching capacity: 120 kA
Size NHG…: 000 to 3
Fuse base: NH fuse bases
(SD = 1 pole, TD = 3 pole)