1 DA1 device series
1.4 Rated operational data
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 15
Inscription Meaning
DA1-124D3FB-A20C Part no.:
DA1 = DA1 series variable frequency drive
1 = Single-phase mains connection / three-phase motor connection
2 = 230 V mains voltage category
4D3 = 4.3 A rated operational current (4-decimal-1, output current)
F = Integrated radio interference suppression filter
B = Integrated brake chopper
A = LED display (7-segment text display)
20 = IP20 degree of protection
C = PCB protection (coated board)
Input
Main terminal rating:
Single-phase AC voltage (U
e
1~ AC)
Voltage 200 - 240 V, frequency 50/60 Hz, input phase current (11 A)
Output
Load side (motor) rating:
Three-phase AC voltage (0 - U
e
), output phase current (4.3 A),
Output frequency (0 - 500 Hz)
Assigned motor output:
0.75 kW with 230 V/1 HP with 230 V for a four-pole, internally cooled or
surface-cooled three-phase motor (1500 min
-1
at 50 Hz/1800 rpm at 60 Hz)
Serial No.: Serial number
IP20 Degree of protection of the housing: IP 20, UL (cUL) Open type
Software Software version (1.20)
08112013 Manufacturing date: 11-08-2013
Max amb. 50 °C Maximum permissible ambient air temperature (50 °C)
Variable frequency drive is an electrical apparatus.
Read the manual (in this case MN04020005Z-EN) before making any electrical
connections and commissioning.