Commissioning the Device in E2E iPro Parameter List • 69
AIC01_2 XEV20_2 - Configuration of Probe 1
Not Used/Discharge 1-6/
Defrost Term 1-6/Return 1-3/Coil Out 1-3
AIC02_2 XEV20_2 - Configuration of Probe 2
AIC03_2 XEV20_2 - Configuration of Probe 3
AIC04_2 XEV20_2 - Configuration of Probe 4
Ofs01_2 XEV20_2 - Probe 1 offset
-100-100
Ofs02_2 XEV20_2 - Probe 2 offset
Ofs03_2 XEV20_2 - Probe 3 offset
Ofs04_2 XEV20_2 - Probe 4 offset
AIT01_2 XEV20_2 - Sensor Type of Probe 1 CPC Thermistor/NTC/PTC/PT1000
AIT02_2 XEV20_2 - Sensor Type of Probe 2 CPC Thermistor/NTC/PTC/PT1000
AI0304_TYPE_2 XEV20_2 - Probe 3 and Probe 4 type Resistive/Voltage/Current
AIT03_2 XEV20_2 - Sensor Type of Probe 3 CPC Thermistor/NTC/PTC/PT1000/
0-1VDC/0-5VDC/0-10VDC/0-20mA/
4-20mA
AIT04_2 XEV20_2 - Sensor Type of Probe 4
AI03_2_min XEV20_2 - Probe 3 value at min
Selectable based on probe type
AI03_2_max XEV20_2 - Probe 3 value at max
AI04_2_min XEV20_2 - Probe 4 value at min
AI04_2_max XEV20_2 - Probe 4 value at max
XEV20_1_VT XEV20_1 - Valve Motor Type
Unipolar/Bipolar Wave/Bipolar Normal
XEV20_2_VT XEV20_2 - Valve Motor Type
Table 16-1 - iPro Parameter List