Electronics Verification
March 2016
Reference Manual
00809-0100-4772, Rev FA
156
Electronics Verification
Equation
Conditions
C
x
= the unit conversion using density (ρ) (see Table C-1 on page 156)
Equation
Unit conversion table (user units to gal/s)
Use the following table to assist with calculated frequencies when using user-defined units.
Table C-1. Unit Conversions.
ρ=operating density
C
x
Units (act) Conversion factor
C
1
gal/s 1.00000E+00
C
2
gal/m 1.66667E-02
C
3
gal/h 2.77778E-04
C
4
Impgal/s 1.20095E+00
C
5
Impgal/m 2.00158E-02
C
6
Impgal/h 3.33597E-04
C
7
l/s 2.64172E-01
C
8
l/m 4.40287E-03
C
9
l/h 7.33811E-05
C
10
m
3
/m 4.40287E-00
C
11
m
3
/h 7.33811E-02
C
12
ft
3
/m 1.24675E-01
C
13
ft
3
/h 2.07792E-03
C
14
bbl/h 1.16667E-02
C
15
kg/s C
10
360/ρ
C
16
kg/h C
11
/ρ
C
17
lb/h C
13
/ρ
C
18
shTon/h C
17
×2000
C
19
mTon/h C
16
×1000
C
20
SPECIAL C
x
/(special units conversion factor)
M
F
K
ρ C×
-------------------=
M
F
K C
x
×
---------------
=