22
4.2TechnicianParameters
4.2.1System
Note-1: NOR/PULS:Normal/Pulse
CTratio
Loadcurrenttransformerstransferratio(Primarycurrent/Secondarycurrent)valuemustbeenteredto
thisparameter.
Example:
IfCurrent TransformerPrimary=500A andCurrent TransformerSecondary=5A,Current Transformer
RatioshouldbeenteredCT Primary/CT Secondary=100.
PTratio
Definesthescalingfactorappliedtovoltagereadoutandassociatedfaultconditions.
ThisPT ratioisforadditionalvoltagetransformersmountedtheunit.
Min
Default
Unit
BREAKERS ( )System->Breakers
Max
HardwareBreakerSelection
GenCloseBreakerRelay Type
GenClose Timer
1
GenOpenBreakerRelay Type
0(dis) 3
GenOpen Timer
NOR/PULS
5
1 250
0
Sec
0
NOR/PULS
1 250
5
0.0
0.0
0
10.0
10.0
250
2
BreakerClosePulse Time
BreakerOpenPulse Time
Transfer Time
SpringLoading Time
RetryNumber
Gen.brk.cls.relay
Gen.brk.cls.time
Gen.brk.open relay
Gen.brk.open time
Type of Breaker
Break.close puls.time
Transfer time
Spring loading time
Retry number
Break.open pulse time
Sec
0.5
0.5
Sec
Sec
Sec
Sec
3
5
1 250
1 250
HardwareBreakerSelection
Genbreakerhasonlyclosedriveandifclosedriveoffbreakerwillopen.
Parameters;GENCLOSE TIMER(ifgenclosedinputselected),GENOPEN TIMER(ifgenclosedinput
selected), TRANSFER TIME.
1- Breakers:
Min
Default
Max
Current TransformerRatio
Voltage TransformerRatio
Select ACsystem;
GeneratorkVA ratingset
CTratio
PTratio
Typeof ACsystem
GeneratorkVA rating
Unit
SYSTEM NETWORK ( )System->Network
3
9999
50
kVA
0
0
1
1
300
1
0-1Phase2Wire
1-3Phase4Wire
2-2Phase3WireL1-L2
3-2Phase3WireL1-L3
99995
100