Min
Default
START TIMERS ( )Timers->Start timers
Max
RemoteStartDelay
Pre-Heat
Pre-HeatBypass
4
0 3600
3
0 250
0
0 250
SafetyOnDelay
5
0 99
HornDuration
60
0(dis) 999
ChargeExcitation Time
15
0 99(cont)
CoolingFan Time
180
0 250
Remote start delay
Pre-heat
Pre-heat bypass
Safety on delay
Horn duration
Chg. excitation time
Cooling fan time
RemoteStartDelay
Pre-Heat
Pre-HeatBypass
SafetyOnDelay
WarmupTime
HornDuration
ChargeExcitationTime
Thistimerdictateshowlongtheunitwillwaitafterithasreceivedaremotestartsignalbeforeitwill
attempttostart. Thispreventun-necessarystartingonafluctuatingmainssupplyetc.
Thisfeatureallowstheunittostartahotenginewithoutperforminganun-necessarypre-heatdelay.
Thebypasstimeristriggeredbythegeneratorstartingandactuallybeingloaded.Ifthegenerator
startedbutdoesnotachieveloadingthenthetimerwillnotbetriggered. Thebypasstimerisinitiated
oncetheenginehascometorest.Ifanyattemptstostartarerequestedwithinthedurationofthe
bypasstimerthestartsequencewillbypassthepre-heattimer.
ThistimerdictateshowlongtheunitwillignoretheLowOilPressure,HighEngine Temperature,
Underspeed,Undervoltsandanyotherinputsconfiguredasactivefromsafetyon.Itallowsthevalues
suchasoilpressuretorisetotheiroperatingvaluesonstartingwithouttriggeringanalarm.Oncethe
timerhasexpiredallalarmconditionsaremonitoredagain.Ifconfiguredtouse'fastloading',shouldall
themonitoredconditions,suchasoilpressure,cometoexpectedstatepriortotheendofthesafetyon
timer,thetimerwillbeterminatedprematurelyensuringmaximumprotectionassoonaspossible.
Thistimerisinitiatedoncetheengineisupandrunning.Itdelaysloadingthegeneratoruntilithas
stabilised.Oncethistimerisexpiredthe'Closegenerator'signalwillbegivenandthegeneratoris
availabletobeloaded.
Thistimerdictateshowlongthehornwillworkafterthelasterrordetected.Onceafterthistimerended
unitwilldohornreset.
Thistimerdictatesthedurationthatthepre-heatoutputwillbeactivebeforeanattemptismadeto
starttheengine.Oncethistimerisexpiredcrankingwillcommence.
Chargeexcitationwasselectableasmomentary/continuousoperation.Thistimerdictateshowlong
theChargeexcitationwillactive.
Unit
Min
Sec
Sec
Sec
Sec
Sec
Sec
IdleMode Time(SmokeLimiting)
dis
3600
Idle mode time
IdleMode TimeOff(SmokeLimitingOff)
Idle mode time off
Sec
Sec
0(dis)
0 250 5
Note: dis=disablecont=continuous
55
4.2.6Timers
Warmup Time
3
0 250
Warming up time
Sec