33
Note: dis=disable
Min
Default
ENGINE MAINTENANCE ( )Engine->Maintenance
Max
RunningHoursInterval
MaintenanceDateInterval
ForceEngineShutdownWhenMaintenanceIsDue
EngineRunningHour(Lsb)
5000
EngineRunningHour
0(dis) 9999
EngineRunningHour(Msb)
ENABL/DISBL
0
0 255
DISBL
0
0
0(dis)
12 6
0 255
0 14
Maint.date interval
Eng. stop when maint
Eng.running hour(lsb)
Eng.running hour
Eng.running hour(msb)
Running hour interval
Unit
Hour
Month
MaintenanceOkay
NO
Maintenance okay
YES/NO
Theusercanchangetheenginerunninghoursvaluebyusingtheseparameters(EngineRunning
Hour(Lsb),EngineRunningHourandEngineRunningHour(Msb)).
iftheenginerunninghourswaschanged75112hours,thevaluesofthese
parameterswascalculatedasfollows;
=75112/65536
=
IntermediateValue=75112–(EngineRunningHour(Msb)*65536)
=75112–(1*65536)
=9576.
=IntermediateValue/256
=9576/256
=
=IntermediateValue–(EngineRunningHour*256)
=9576–(37*256)
=
Forexample;
EngineRunningHour(Msb)
1
EngineRunningHour
37
EngineRunningHour(Lsb)
104
Min
Default
LOAD TEST ( )Engine->Load test
Max
Unit
0-DISABLE
Disable/enable select
Disable,NoLoadorOnLoadSelection
0-DISABLE
1-NOLOAD
2-ONLOAD
Disable,NoLoadorOnLoadSelection
DISABLE T disable
NOLOAD
ONLOAD T
estmode .
Thegeneratorwillberunningwithouttakingtheloadintestmode.
hegeneratorwillberunningwithloadintestmode.
:
:
: