25
TransferTime
SpringLoadingTime
RetryNumber
Thisisusedtoallowforfixeddurationtransferbreakswhenswitchingfrommainstogeneratorandback.Itcan
beusedtoensurethatthesupplyisremovedfromtheloadforfixedperiodoftimetoallowpumps/motorsto
cometorestetc.
Whentheunitgiveopencommandtothebreakerandafterthattheunitwanttogiveclosecommandthesame
breaker,thistimeforbetweenopenandclosecommands,becauseifthereisnodelaybetweenopenandclose
commandscanbeproblemthemotorizedswitches.
Theunittrytoclosebreakernumberofthisparameter.Ifeachtrythereisnoclosefeedback,afterlasttrythe
alarmwillbeactivated.
Min
Default
Unit
LCD DISPLAY ( )System->LCD display
Max
LanguageSelection
DigitalContrast
ENGLISH/CHINESE
5
4 9
Contrast
Language
*
6
Auto Scroll Time
Auto ScrollNumber
Scroll TimeForErrorMessages
0
0(dis) 250
Sec
3
9
2
1 250
Auto scroll number*
7
Err. mesg scroll time
Auto scroll time
Sec
1
ENGLISH
Language Selection
Digital Contrast
Auto Backlight Off
Scroll Time
Scroll Number
Scroll Time For Error Messages
Auto
Auto
Language selection: English or Chinese.
It is used to change contrast of LCD Display.
ENABL: If any button is not pressed for 60 secs, LCD backlight will be automatically changed to power saving mode.
DISBL: LCD backlight is on continuously.
The scroll time between all data display pages.
The number of data display pages that will be scrolled.
Error messages are displayed the last line of LCD Display. If more than one error condition is present, each of them
is displayed during time defined by Auto Scroll Timer parameter.
Note: =Selectablevalueofthisparameteris“ENGLISH/TURKISH”at
Trans-MiniAUTO.XXX(TR)devices.
=Max.valueofthisparameterisequalto15at Trans-MiniAUTO.CANdevices
*
*
6
7
dis=disable
Min
Default
Unit
COMMUNICATION ( )System->Communication
Max
Slave Address
1
1 247
0
5 3
BaudRate
0-1200baud
1-2400baud
2-4800baud
3-9600baud
4-19200baud
5-38400baud
StopBit(0->1stopbit,1->2stopbit)
0
2
0
0 1 0
Slave address
Baud rate
Parity
Stop bit
Parity
0-
1-
2-
NONE
ODD
EVEN
AutoBacklightOff
Auto backlight off
DISBL/ENABL DISBL