29
Min
Default
Unit
ENG. CRANK DISCONNECT ( )Engine->Crank disconnect
Max
CrankDisconnectOnGen.Frequency
CrankDisconnectOnGen.Voltage
CrankDisconnectOnCharge Alt.Voltage
30.0
CrankDisconnectOnOilPressure
25.0 75.0
Hz
500
500 6000
RPM
300
60(dis) 600
VV
dis
6.0(dis) 30.0
VZ
dis
1.0(dis) 30.0
BAR
Generator frequency
Engine speed
Generator volt
Alt. Charge volt
Oil pressure
CrankDisconnectOnEngineRPM
Theparametersinthispageareusedforenginestartedsignals.Ifanyoftheselectedsignalsappears,
theunitassumesthattheenginehasstarted.
Ifthegeneratorfrequencyoverthan30.0Hz,theunitassumesthattheenginehasstartedandtheunit
stopcranking.
Ifthegeneratorspeedoverthan500Rpm,theunitassumesthattheenginehasstartedandtheunit
stopcranking.
Ifthegeneratorvoltageoverthan300Vac,theunitassumesthattheenginehasstartedandtheunit
stopcranking.
Ifthechargealternatorvoltageoverthan6.1Vdc,theunitassumesthattheenginehasstartedand
theunitstopcranking. Ifthechargegeneratorinput(terminal#13)isdisconnect,thisparameter
selectedasdisabled(6.0Vdc).
Iftheoilpressuresenderoverthanthisvalueortheoilpressuredigitalinput(terminal#15)isnot
switchedto-Battery,theunitassumesthattheenginehasstartedandtheunitstopscranking.
CrankDisconnectOnGen.Frequency
CrankDisconnectOnEngineRPM
CrankDisconnectOnGen.Voltage
CrankDisconnectOnCharge Alt.Voltage
CrankDisconnectOnOilPressure
Note:
Min
Default
Unit
ENGINE SPEED SETS ( )Engine->Speed settings
Max
EngineUnderSpeedShutdown
EngineUnderSpeedPrealarm
EngineUnderSpeedPrealarmReset
dis
EngineOverSpeedShutdown
500(dis) 5000
500(dis)
RPM
500
500 5000
EngineOverSpeedPrealarmReset
EngineSpeedShutdownDelay Time
500
1.0
RPM
RPM
RPM
RPM
RPM
Sec
5000
500(dis) 5000
5000
5000
10.0
EngineOverSpeedPrealarm
Under speed shutdown
Under speed prealarm
Under speed reset
Over speed shutdown
Over speed prealarm
Over speed reset
Shutdown delay time
500
0.0
Theparametersinthispageareusedforthegeneratorspeedlowandhighalarms.
NominalSpeed
1500
500 5000
RPM
Nominal speed
dis
dis
dis
500(dis)
Min
Default
ENGINE PLANT BATTERY ( )Engine->Plant battery
Max
BatteryUndervoltsWarning
BatteryUndervoltsWarningReset
BatteryUndervoltsVoltsDelay
BatteryOvervoltsWarning
10.0
BatteryOvervoltsWarningReset
6.0(dis) 30.0
10.5
6.0
1.0
0.0 9.9
30.0
29.5
Charge AlternatorWarning
dis
30.0
30.0
6.0 30.0
BatteryOvervoltsDelay
1.0
0.0
9.9
30.0
6.0(dis)
6.0(dis)
Under volt
Under volt reset
Under volt delay
Over volt
Over volt reset
Over volt delay
Alt. chg. warning
Unit
VZ
VZ
VZ
VZ
Sec
Sec
VZ
Theparametersinthispageareusedforthebatteryvoltagelowandhighalarmsandthecharge
alternatorvoltagewarning.