5.Specifications
60
Equipmentuse
Housing&Mounting
PanelCut-Out
Protection
Weight
Environmentalrating
Operating/StorageTemperature
Operating/StorageHumidity
InstallationOverVolt.Category
PollutionDegree
ModeofOperation
CrankingDropouts
BatteryVoltageMeasurement
GeneratorVoltageMeasurement
GeneratorFrequency
SenderMeasurement
:Electricalcontrolequipmentforgeneratingsets.
:111mmx81mmx61mm.(includingconnectors)
.
:81mmx70mm.
:
: Approximately0,3Kg.
:
withnon-condensinghumidity
:-20°Cto+70°C/-30°Cto+80°C
:90%max.(non-condensing)
:II Appliances,portableequipment
:II,Normalofficeorworkplace,nonconductivepollution
:Continuous.
:8to32V .Max.operatingcurrentis360mA.
:Batteryvoltagecanbe“0”VDCformax.50msduring
cranking(batteryvoltageshouldbeatleastnominal
voltagebeforecranking).
:8to32V ,accuracy:1%FS,resolution:0,1V
:3
Resolution:1V.
:5to99.9Hz(min.20VACPh-N) Accuracy:0,25%FS,
Resolution:0,1Hz.
:5A.
:
: .
:0to1300ohm,accuracy:1%FS,resolution:1ohm.
.Plastic
housingforpanelmounting
IP65atfrontpanel.
Standard,indooratanaltitudeoflessthen2000meters
.
to300VACPh-N,5to99.9Hz. Accuracy:1%FS,
DCBatterySupplyVoltage Z
Z
Z
MagneticPickupInput
TransistorOutputs
:35to10000Hz(4to35voltspeakcontinuously).
Accuracy:0,25%FS.(Onlyavailableat
Trans-MiniAUTO.MPUdevices)
CanBuscommunicationwith1939ECU(Only
availableat Trans-MiniAUTO.CANdevices)
:FuelorConfigurableoutput-11A atDCsupplyvoltage
CrankorConfigurableoutput-21A atDCsupplyvoltage
Configurableoutput-31A atDCsupplyvoltage
Configurableoutput-41A atDCsupplyvoltage
Configurableoutput-51A atDCsupplyvoltage
Configurableoutput-61A atDCsupplyvoltage
AlltransistorouputssuppliedfromDCsupplyterminal12
Approvals :
CTsecondary
ChargeGeneratorExcitation
ChargeGen.Vol.Measurement
Communicationinterface
210mA @12V,105mA @24V.Nominal2.5W.
8to32V ,accuracy:1%FS,resolution:0,1V
:RS-232,
,