32
Note: =Parametersinthistableareonlyavailableat Trans-MiniAUTO.CAN
dis=disable
*
10
Min
Default
Unit
CANBUS ERROR SET ( )Engine->CanBus error set *
10
Max
CanFault Actions:
0-Disable
1-WarningNon-Latching
2-Warning(AlarmOnly,NoShutdown)
3-Electrical Trip(Alarm/OffLoadGenerator
FollowedByShutdown AfterCooling)
4-Shutdown(Alarm AndShutdown)
0
0 2
0
0(dis) 4
CAN fault activation
CANfaultactions
SecCanFaultDelay
10
2 250
CAN fault delay
CanFault Activation:
0- ActiveFromStarting
1- ActiveFromSafetyOn
2- Always Active
J1939 AmberWarningLamp Actions:
0-Disable
1-WarningNon-Latching
2-Warning(AlarmOnly,NoShutdown)
3-Electrical Trip(Alarm/OffLoadGenerator
FollowedByShutdown AfterCooling)
4-Shutdown(Alarm AndShutdown)
2
0 2
0
0(dis) 4
Amber warn.activation
Amberwarn.actions
SecJ1939 AmberWarningLampDelay
2
0 250
Amber warn.delay
J1939 AmberWarningLamp Activation:
0- ActiveFromStarting
1- ActiveFromSafetyOn
2- Always Active
J1939RedStopLamp Actions:
0-Disable
1-WarningNon-Latching
2-Warning(AlarmOnly,NoShutdown)
3-Electrical Trip(Alarm/OffLoadGenerator
FollowedByShutdown AfterCooling)
4-Shutdown(Alarm AndShutdown)
2
0 2
0
0(dis) 4
Red stop activation
Redstopactions
SecJ1939RedStopLampDelay
2
0 250
Red stop delay
J1939RedStopLamp Activation:
0- ActiveFromStarting
1- ActiveFromSafetyOn
2- Always Active