EasyManua.ls Logo

EMKO TRANS MINI AUTO - Сonfigurable Inputs Selections

EMKO TRANS MINI AUTO
61 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CONFIGURABLEINPUTSSELECTIONS
0REMOTESTARTONLOAD
3
6SIMULATE AUTOBUTTON
7SIMULATETESTBUTTON
9SIMULATESTARTBUTTON
10SIMULATESTOP BUTTON
11GENERATORCLOSED AUXILIARY
In AUTOmode,ifoneoftheconfigurableinputsareselectedas0(RemoteStartOnLoad)andthisinputis
active,thentheunitwillperformthestartsequenceandtransferloadtothegenerator.Iftheinputispassive,the
unitwillperformthestopsequence.
Ifthisinputisactive,operationwillbesimilartothe‘RemoteStartOnLoad’ functionexceptthatthegeneratorwill
notbeinstructedtotaketheload. Thisfunctioncanbeusedwhereanengineonlyrunisrequirede.g.for
exercise.
Thisinputisusedtopreventtheunitfromloadingthegenerator.Ifthegeneratorisalreadyonload,activating
thisinputwillcausetheunittounloadthegenerator.Removingtheinputwillallowthegeneratortobeloaded
again. Thisinputonlyoperatestocontrolthegenerator-switchingdeviceiftheunitloadswitchinglogicis
attemptingloadthegenerator.
Whenmoduleinthe AUTOmode.Intheeventofaremotestart,thegeneratorwillbeinstructedtostartandtake
load.Onremovaloftheremotestartsignal,themodulewillcontinuetorunthegeneratoronloaduntilthis AUTO
RESTOREINHIBIT inputisremoved.Oncetheinputisremovedtheunitwilltakeofftheloadandsupplyand
followanormalgeneratorstopsequence.
Thisinputisusedtoprovideanover-ridefunctiontopreventtheunitfromstartingthegeneratorintheeventofa
remotestartoccurring.Ifthisinputisactiveandaremotestartsignaloccurstheunitwillnotgiveastart
commandtothegenerator.Ifthisinputsignalisthenremoved,theunitwilloperateasifaremotestarthas
occurred,startingandloadingthegenerator.Ifthe'AutoStartInhibit'signalbecomeactiveoncemoreitwillbe
ignoreduntiltheunitshutdownthegenerator.
1REMOTESTARTOFFLOAD
2
4
5
8
12GENERATORLOADINHIBIT
Note:
13
14
15 AUTORESTOREINHIBIT
16 AUTOSTARTINHIBIT
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
Thisinputmimic'stheoperationofthe'Auto'buttonandisusedtoprovidearemotelylocated Automodepush
button.
Thisinputmimic'stheoperationofthe'Test'buttonandisusedtoprovidearemotelylocated Testmodepush
button.
Thisinputmimic'stheoperationofthe'Start'buttonandisusedtoprovidearemotelylocatedstartpushbutton.
Thisinputmimic'stheoperationofthe'Stop'buttonandisusedtoprovidearemotelylocatedStoppushbutton.
Thisinputisusedtoprovidefeedbacktoallowtheunittogivetrueindicationofthecontactororcircuitbreaker
switchingstatus.Itshouldbeconnectedtothegeneratorloadswitchingdeviceauxiliarycontact.
45

Table of Contents