17PANEL LOCK
Note:
18
19
20
21
22REMOTEINHIBIT
23
24
25LOWOIL PRESSURE
26HIGHTEMPERATURE
27EMERGENCY STOP
Thisinputisusedtoprovidesecuritytotheinstallation.Ifthepanellockinputisactive,theunitwillnotrespondto
operationofthemodeselectorstartbuttons. Thisallowstheunittobeplacedintoaspesificmode(suchas
Auto)andthansecured. Theoperationoftheunitisnotaffectedandtheoperatorwillstillbeabletoviewthe
variousinstrumentationpagesetc. Externalcontrolsources(i.e.SimulateStartButton)arenotaffectedby
thepanellockinputandwillcontinuetooperatenormally.
In AUTOmode,ifoneoftheconfigurableinputsareselectedas22(RemoteInhibit)andthisinputisactive,the
modulewillinhibitthegeneratorforstarting.Intheotherhand,ifthisinputisactivewhilethegeneratorwas
starting,themodulewillstopthegenerator.
Thisinputisusedastheoilpressurefailureinput.
Thisinputisusedasthetemperaturefailureinput.
Thisinputisusedastheemergencystopinput.
Thisinputisusedastheoillevelfailureinput.Itwon’tbecheckedwhilestartingorstoppingattemps.
RESERVED
RESERVED
RESERVED
RESERVED
BEINGFOUND ALIVE
RESERVED
28-LOWOIL LEVEL
Whenthisinputisactive,controllingtheengineremotelyisnotpossible.
46