Min
Default
STOPPING TIMERS ( )Timers->Stopping timers
Max
RemoteStopDelay
Cooling Time
4
0 250
60
0(dis)
3600
Fail ToStop Time
30
15 99
Remote stop delay
Cooling time
Fail to stop delay
RemoteStopDelay
CoolingTimer
FailToStopTime
Thistimerdictateshowlongtheunitwillwaitafterithasreceivedaremotestopsignalbeforeitwill
attempttostop. Thispreventun-necessarystoppingonafluctuatingmainssupplyetc.
Oncetheunithasgivenashutdownsignaltotheengineitexpectstheenginetocometorest.It
monitorstheOilpressureandspeedsensingsourcesandiftheystillindicateenginemovementwhen
thistimerexpiresa'Fail ToStop'alarmsignalisgenerated.
Thisisthetimethegeneratoristorunoff-loadoncetheloadtransfersignalhasceased. Thisgivesthe
enginetimetocooldownbeforeshutdown.
Unit
Sec
Sec
Sec
CoolingFanTime
IdleModeTime(SmokeLimiting)
IdleModeTimeOff(SmokeLimitingOff)
ThistimerdictateshowlongtheCoolingFanwillcontinuetooperate.
Thisistheamountoftimethatthesmokelimitingoutputwillremainactiveforoncetheenginehas
started.Whilethesmokelimitingoutputisactivetheenginewillbeheldatareducedspeedto
minimisesmokeemissionsonstart-up.(OnlyiffittedwithanappropriateElectronicControlModule).
Oncethetimerhasexpiredtheenginewillbeallowedtoaccelerateuptoitsnormaloperatingspeed.
ThistimerisstartedaftertheIdlemodetimer(smokelimittimer)wasexpired. Thisistoallowthe
enginetoacceleratetoitsnormalrunningspeedwithouttriggeringanunderspeedalarm,etc.
56