EMKO TRANS MINI AUTO - Stopping Timers; Idle Mode Time (Smoke Limiting); Idle Mode Time off (Smoke Limiting Off); Remote Stop Delay

EMKO TRANS MINI AUTO
61 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Min
Default
STOPPING TIMERS ( )Timers->Stopping timers
Max
RemoteStopDelay
Cooling Time
4
0 250
60
0(dis)
3600
Fail ToStop Time
30
15 99
Remote stop delay
Cooling time
Fail to stop delay
RemoteStopDelay
CoolingTimer
FailToStopTime
Thistimerdictateshowlongtheunitwillwaitafterithasreceivedaremotestopsignalbeforeitwill
attempttostop. Thispreventun-necessarystoppingonafluctuatingmainssupplyetc.
Oncetheunithasgivenashutdownsignaltotheengineitexpectstheenginetocometorest.It
monitorstheOilpressureandspeedsensingsourcesandiftheystillindicateenginemovementwhen
thistimerexpiresa'Fail ToStop'alarmsignalisgenerated.
Thisisthetimethegeneratoristorunoff-loadoncetheloadtransfersignalhasceased. Thisgivesthe
enginetimetocooldownbeforeshutdown.
Unit
Sec
Sec
Sec
CoolingFanTime
IdleModeTime(SmokeLimiting)
IdleModeTimeOff(SmokeLimitingOff)
ThistimerdictateshowlongtheCoolingFanwillcontinuetooperate.
Thisistheamountoftimethatthesmokelimitingoutputwillremainactiveforoncetheenginehas
started.Whilethesmokelimitingoutputisactivetheenginewillbeheldatareducedspeedto
minimisesmokeemissionsonstart-up.(OnlyiffittedwithanappropriateElectronicControlModule).
Oncethetimerhasexpiredtheenginewillbeallowedtoaccelerateuptoitsnormaloperatingspeed.
ThistimerisstartedaftertheIdlemodetimer(smokelimittimer)wasexpired. Thisistoallowthe
enginetoacceleratetoitsnormalrunningspeedwithouttriggeringanunderspeedalarm,etc.
56
Note: dis=disable