49
CONFIGURABLEOUTPUTSSELECTIONS
Outputisnotused
Theoutputindicatesthattheinternalsounderisoperating.Itmaybeuseforexternalsounder.
Thisoutputindicatesthatadigitalinputthathasbeenconfiguredas'autostartinhibit'isactive.
Thisoutputindicatesthatabatteryhighvoltagealarmhasoccurred.
Thisoutputindicatesthatabatterylowvoltagealarmhasoccurred.
Thisoutputindicatesthatachargingalternatorfailurehasoccurred.
Thisoutputindicatesthatawarning,electricaltriporshutdownalarmhasbeenactivated.
Thisoutputindicatesthatanelectricaltripalarmhasbeenactivated. Thisoutputcanonlyberesetbyremovalof
thefaultandbythenpressingtheRESET button.
Thisoutputindicatesthatashutdownalarmhasbeenactivated. Thisoutputcanonlyberesetbyremovalofthe
faultandbythenpressingtheRESET buttonorbyusinganexternal'alarmreset'input.
0NOTUSED
3 AUDIBLE ALARM
4 AUTOSTARTINHIBIT
5RESERVED
6BATTERY HIGHVOLTAGE
7BATTERY LOWVOLTAGE
8
11CHARGE ALTERNATORFAILURE
12COMMON ALARM
13COMMONELECTRICAL TRIP ALARM
14COMMONSHUTDOWN ALARM
1 AIRFLAP CONTROL
2 ALARMRESET
RESERVED
9 ECUPOWER(onlyavailableatTrans-MiniAUTO.CAN)
10CANECUSTOP (onlyavailableatTrans-MiniAUTO.CAN)
15COMMONWARNING ALARM
16COOLINGFAN AFTERSTART
Normallyusedtocontrolanairflap,thisoutputbecomesactiveuponanEngineshutdownfailuresituation.
Inactivewhenthesethascometorest.
Theoutputindicatesthatanalarmresetbeingperformed.Oncethealarmresethasbeencompleted,theoutput
becomeinactiveagain. Theoutputcouldbeusedtogiveanexternalresetsignaltoexternalsystems.
ThisoutputnormallyusedtoturnontheECU(sometimesviaanexternalslaverelay).SomeengineECUsare
permanentlypoweredinwhichcasetheECUPoweroutputisusedtogiveinputtoaRun(orsimilarlynamed)
inputontheECU.
ThisoutputusedtogiveinputtoaStop(orsimilarlynamed)inputontheECU. Thisisusedasabackupstop
systemshouldtheECUDatalinkfail.Inthisinstance,itisnotpossibletostoptheengineusingadatacommand
asthelinkisnotoperative. Asabackup,theSTOP signalisgiventotheengineviaaseparatehardwired
connection.
Thisoutputindicatesthatawarningalarmhasbeenactivated. Thisoutputisnormallyself-resettingonremoval
ofthefault.
Thisoutputshouldenergiseassoonasenginehasstartedsothefanshouldberunningwhentheengineis
running. ThisoutputshouldcontinuetooperateforCoolingFan Timeparameterafterenginehasstopped.
CAN
17COOLINGFAN AFTERSTOP
ThisoutputindicatesthatcanbemadetoenergiseforCoolingFan Timeparameteraftertheengineshutsdown
(torunanelectriccoolingfanontheradiator).