Note: *
8
= Theseparametersareonlyavailableat Trans-MiniAUTO.MPU
dis=disable
28
SensingOptionsGeneratorFrqEn/Dis
SensingOptionsPickupEn/Dis&Flywheel
AllWarnings AreLatchedEn/Dis
ENABLE:Speedsensingwillbederivedfromthegeneratoroutputfrequency.
DISABLE:Speedsensingnotwillbederivedfromthegeneratoroutputfrequency.
ENABLE:Warningsandpre-alarmswilllatchedwhentriggered. Toresetthealarmeitheranexternal
resetmustbeappliedtooneoftheinputsorthe'Reset'pushbuttonoperated,oncethetriggering
conditionhascleared.
DISABLE:Normaloperation,thewarningsandpre-alarms(exceptspareinputs,becausetheyhave
theirlatchingornon-latchingselections)willautomaticallyresetoncethetriggeringconditionhas
cleared.
DISABLE:Speedsensingwillnotbederivedfromthemagneticpickup.
1-1000:Speedsensingwillbederivedfromthemagneticpickupandthenumberisflywheel
teethontheengine.
Min
Default
Unit
GENERATOR GENERAL ( )Generator->General
Max
SensingOptionsGeneratorFrqEn/Dis
Sens.option gen.freq
ENABL
ENABL/DISBL
0( )dis
SensingOptPickupEn/Dis&Flywheel
DISBL1000
AllWarnings AreLatchedEn/Dis
Sens.opt.pickup&flywh*
8
All warning are latch
ENABL/DISBL DISBL
4.2.3Engine
ENABL/DISBL
Sec
Min
Default
Unit
ENGINE START OPTIONS ( )Engine->Starting options
Max
Audible AlarmPrior ToStartingEn/Dis
NumberOfStart Attempts
Cranking Time
CrankRest Time
DISBL
3
5
1
1
10
99
10
5 99
PickupSensorFailDelay(Pickup)
3.0
0.1 10.0
Horn prior start
No. of crank attemp
Cranking time
Crank rest time
Pickup fail delay*
8
Sec
Sec
Audible AlarmPriorToStartingEn/Dis
NumberOfStart Attempts
CrankingTime
CrankRestTime
ENABLE: Theaudiblealarmwillsoundbeforetheenginestarts. Thesounderwillbecomeactiveonce
thestartdelayisinitialised,itwillremainactiveuntileithertheenginereachescrankdisconnectspeed
orpre-heattimersarecancelled.
Thisvalueisthenumberoftimesthemodulewillattempttostartthegenerator.Shouldthegenerator
startthemodulewillnotattemptfurtherstarts.Ifthegeneratordoesnotstartafterthefinalattempt,the
modulewillgivea‘Failtostart’ alarm.
Thisistheamountoftimethemodulewillwaitforbetweenstartattempts. Thisistoallowthestarter
motortocoolandthestarterbatteriestorecover.
Thisisthemaximumamountoftimethatthemodulewillenergisethestartermotorforduringstarting
attemptsoncethestarterhasengaged.