EasyManua.ls Logo

EMKO TRANS MINI AUTO - Сonf. Input-1

EMKO TRANS MINI AUTO
61 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Min
Default
Unit
CONF. INPUT-1 ( )Inputs->Conf. input-1
Max
1
2
20(dis)
10
4
20
0
2500
Sec
0
2
0
28 27
0
Dis,user conf.or list
Polarity
Indication
Activation
Select from list
Active delay
0-Disable
1-UserConfigured
2-SelectFromList
0-NormallyOpen(Close To Activate)
1-NormallyClose(Open To Activate)
IfUserConfigured
0-Status
1-WarningNon-Latching
2-WarningLatching
3-Electrical Trip
4-Shutdown
IfUserConfigured
0- ActiveFromStarting
1- ActiveFromSafetyOn
2- Always Active
IfSelectFromList
0-RemoteStartOnLoad
1-RemoteStartOffLoad
2-Reserved
3-Reserved
4-Reserved
5-Reserved
6-Simulate AutoButton
7-Simulate TestButton
8-Reserved
9-SimulateStartButton
10-SimulateStopButton
11-GeneratorClosed Auxiliary
12-GeneratorLoadInhibit
13-Reserved
14-Reserved
15-AutoRestoreInhibit
16-AutoStartInhibit
17-PanelLock
18-Reserved
19-Reserved
20-Reserved
21-Reserved
22-RemoteInhibit
23-BeingFound Alive
24-Reserved
25-LowOilPressure
26-High Temperature
27-EmergencyStop
28-LowOilLevel
Input active delay
42
Note: dis=disable