51
44GASENGINEIGNITIONOUTPUT
45GENERATOR ATREST
46GENERATOR AVAILABLE
47GENERATORCLOSED AUXILIARY
48GENERATORFAILEDTOCLOSE
49GENERATORFAILEDTOOPEN
50GENERATORHIGHFREQUENCY PRE-ALARM
51GENERATORHIGHFREQUENCY SHUTDOWN
52GENERATORHIGHVOLTAGEPRE-ALARM
53GENERATORHIGHVOLTAGESHUTDOWN
54GENERATORLOADINHIBIT
55GENERATORLOWFREQUENCY PRE-ALARM
56GENERATORLOWFREQUENCY SHUTDOWN
57GENERATORLOWVOLTAGEPRE-ALARM
58GENERATORLOWVOLTAGESHUTDOWN
59GENERATORSTOPPING
61HORNOUTPUTLATCHED
62HORNOUTPUTPULSED
63LAMP TEST
Withtheengagingofthestartertheignitiondelayisstarted.Ifthe‘minimumignitionspeed’ isreachedafter
expiryofthistime,theconfigurablerelayoutput‘ignition’ isset.Whenthenecessaryengineshutdownprocess,
firstlygasvalveisde-energised. Thenignitionoutputisde-energisedthatafter5secondswhentheengine
speedbecomelowerthan‘minimumignitionspeed’
Theoutputindicatesthatthegeneratorisnotrunning.
Thisoutputindicateswhenthegeneratorisreadytoacceptload,i.e.aftersafetyonandwarmuptimershave
timedout.
Thisoutputindicatesthatadigitalinputthathasbeenconfiguredas'generatorclosedauxiliary'isactive.
Thisoutputsourcehasintendedtobeusedtoindicateafailureofthegeneratorcontactororbreaker.Itcanonly
beusediftheunitisconfiguredtouse'generatorclosedauxiliary'feedback.
Thisoutputsourcehasintendedtobeusedtoindicateafailureofthegeneratorcontactororbreaker.Itcanonly
beusediftheunitisconfiguredtouse'generatorclosedauxiliary'feedback.
Thisoutputindicatesthatageneratorhighfrequencywarning(pre-alarm)hasoccurred.
Thisoutputindicatesthatageneratorhighfrequencyshutdownhasoccurred.
Thisoutputindicatesthatageneratorhighvoltagewarning(pre-alarm)hasoccurred.
Thisoutputindicatesthatageneratorhighvoltageshutdownhasoccurred.
Thisoutputindicatesthatadigitalinputhasbeenconfiguredas'generatorloadinhibit'isactive.
Thisoutputindicatesthatageneratorlowfrequencywarning(pre-alarm)hasoccurred.
Thisoutputindicatesthatageneratorlowfrequencyshutdownhasoccurred.
Thisoutputindicatesthatageneratorlowvoltagewarning(pre-alarm)hasoccurred.
Thisoutputindicatesthatageneratorlowvoltageshutdownhasoccurred.
Thisoutputindicatesthattheenginehasbeeninstructedtostopbuthasnotcometorest.
Thisoutputusedtocontroltheloadswitchingdevice.ForDetailssee:"BREAKERSPage"section.
Thisoutputindicatesthatthelatchedhornalarmhasoccurred.
Thisoutputindicatesthatthepulsedhornalarmhasoccurred.
60GENERATOROPENBREAKER
Thisoutputindicatesthatthemoduleisperformingalamptest.
64RESERVED

Table of Contents