89PANEL LOCK
90PRE-HEAT(duringpreheattimer)
91PRE-HEAT(untilendofcranking)
92PRE-HEAT(untilendofwarming)
93PRE-HEAT(untilendsafetyon)
94REMOTESTARTPRESENT
95REMOTESTOP DELAY INPROGRESS
96SHORTCIRCUIT
98STARTING ALARM
99STARTING ALARMS ARMED
100STOP RELAY ENERGISED
101SYSTEMIN AUTOMODE
102SYSTEMINMANUAL MODE
103SYSTEMINSTOP MODE
104SYSTEMINTESTMODE
105UNDERCURRENTPRE-ALARM
106UNDERCURRENT ALARM
Thisoutputindicatesthattheunit‘panellock’ isactive.Ifthepanellockinputisactive,theunitwillnotrespondto
operationoftheModeselectorstartbuttons. Thisallowstheunittobeplacedintoaspecificmode(suchas
auto)andthensecured.
Theoutputcontrolsthepre-heater.Pre-heatoutputisavailableforthedurationofpre-heattimer,which
terminatespriortocranking.
Theoutputcontrolsthepre-heater. As'Pre-heat(duringpre-heattimer)'modebutpre-heatisalsoavailable
duringcranking.
Theoutputcontrolsthepre-heater. As'Pre-heat(untilsafetyon)'butpre-heatcontinuestobeavailableuntilthe
warm-uptimerhaselapsed.
Theoutputcontrolsthepre-heater. As'Pre-heat(untilendofcranking)'butpre-heatisalsoavailablewhile
waitingforthedelayedalarmstobecomeactive.
Thisoutputindicatesthatadigitalinputthathasbeenconfiguredas'remotestart'isactive. Thisoutputcouldbe
usedtopasstheremotestartsignalontoelsewhereinthecontrolsystem.
Thisoutputsourcewillbeactivetoindicatethatthereturntimerisrunning.
Thisoutputindicatesthatthemodulehasdetectedashortcircuitonthegeneratoroutput.
Thisoutputisusedtosupplyasmoke-limitingsignaltoanElectronicGovernortolimitsmokeemissionsonstart-
up.ItisusedinconjunctionwiththeSmokelimittimer(Idlemodetimer)settings.Oncethetimerhasexpired,the
Smokelimitoutputwillceasetooperateallowingtheenginetoacceleratetonormalrunningspeed.
Thisoutputisusedtosupplyanexternalsounderwithasignalthattheengineisabouttostart. Theoutputwillbe
activeduringthestartdelayandpre-heattimer(ifused).
Theoutputindicatesthatthestartingalarmsarenowenabled.Itcanbeusedtocontrolexternallogiccircuitry.
Startingalarmsarearmedassoonastheunitcommencesstartingoftheengineandremainarmeduntilthe
engineatrest.
Theoutputmimicstheoperationofthestoprelay.Canbeusedtocontrolexternallogiccircuitry.
Theoutputindicatesthattheunitisinthe Automode.
TheoutputindicatesthattheunitisintheManualmode.
TheoutputindicatesthattheunitisintheStopmode.
Theoutputindicatesthattheunitisinthe Testmode.
Thisoutputindicatesthattheundercurrentpre-alarmhasbeenreached.
Thisoutputindicatesthattheundercurrenttriplevelhasbeenreached.
97SMOKELIMITING