Cerabar M
10 Endress+Hauser
Operating elements The operating elements are located under the optional onsite display on the electronic insert.
Onsite operation 4 to 20 mA functions
• Calibrating the display value (e.g. on the onsite display) to zero
• Setting the lower-range value and upper-range value – reference pressure applied at the device
• Switching damping on and off
4 to 20 mA HART functions
• Calibrating the display value (e.g. on the onsite display) to zero
• Setting the lower-range value and upper-range value – reference pressure applied at the device
• Switching damping on and off
• Performing reset
PROFIBUS PA functions
• Calibrating the display value on the onsite display to zero
• Setting the lower-range value and upper-range value – reference pressure applied at the device
• Setting the bus address of the device
Handheld terminals – HART With a handheld terminal, all the parameters can be configured anywhere along the 4 to 20 mA line via menu
operation.
P01-PMx4xxxx-19-xx-xx-xx-000
Analog electronic insert
➀
Potentiometer for calibrating the lower-range
value (Zero)
➁ Potentiometer for fine adjustment of the span
➂ DIP switches 1 to 3 for coarse adjustment of
the span
➃ DIP switch for damping on/off
➄ Slot for optional onsite display
P01-PMx4xxxx-19-xx-xx-xx-001
4 to 20 mA HART electronic insert
➀ Switch for damping on/off
➁ Key for calibrating the lower-range value
(Zero)
1
➂ Key for calibrating the upper-range value
(Span)
2
➃ Slot for optional onsite display
P01-PMx4xxxx-19-xx-xx-xx-002
PROFIBUS PA electronic insert
➀ DIP switches for bus address
➁ Key for calibrating the lower-range value
(Zero)
1
➂ Key for calibrating the upper-range value
(Span)
2
➃ Slot for optional onsite display
1) Lower-range value (LRV) = Zero
2) Upper-range value (URV) = Span
Display
Span
fine
coarse
Zero
➀➁
➂
➃
➄
+
–
Zero
Damping
on off
Span
Display
➀
➂
➁
➃
+–
on
off
Zero Span
Display
address
➀
➂
➁
➃